Understanding U-Values in Modern Building Extensions
A U-value measures the rate of heat loss through a building element, expressed in Watts per square metre Kelvin (W/m²K). Lower numbers signify superior thermal insulation performance.
Achieving the mandatory 0.18 W/m²K wall target requires modern cavity construction, typically comprising 100mm facing brick, a 100mm cavity filled with rigid foil-faced PIR insulation or injected EPS beads, and 100mm lightweight aerated thermal blockwork.
| Building Element | Pre-2022 Standard | Current Part L Target | Typical Specification |
| External Cavity Walls | 0.28 W/m²K | 0.18 W/m²K | 100mm PIR full-fill cavity insulation |
| Pitched Roof (Insulated at Rafter) | 0.18 W/m²K | 0.15 W/m²K | 125mm PIR between rafters + 37.5mm under |
| Flat Roof Deck | 0.18 W/m²K | 0.15 W/m²K | 130mm rigid PIR warm roof insulation board |
| Solid Floor Slab | 0.22 W/m²K | 0.18 W/m²K | 120mm PIR board beneath concrete screed |
| Windows & Bifold Doors | 1.6 W/m²K | 1.4 W/m²K | Thermally broken aluminium with argon gas |
- External walls: Maximum 0.18 W/m²K (requires 100mm rigid PIR insulation).
- Pitched roof ceiling: Maximum 0.15 W/m²K (150mm PIR between and under rafters).
- Ground floor slabs: Maximum 0.18 W/m²K (120mm PIR beneath screed).
- Glazing and bifolds: Maximum 1.4 W/m²K (argon-filled Low-E double glazing).
The 25% Glazing Allowance Rule
Modern open-plan kitchen extensions frequently incorporate wide aluminium bifold doors and large glass roof lanterns. However, Part L limits the total area of new glazing to no more than 25% of the extension floor area.
For example, a 30m² extension is permitted 7.5m² of new glazing, plus the area of any existing house windows covered by the extension. If your proposed bifold doors and roof lantern exceed this limit, you must prove compliance using compensatory energy modeling.
SAP Energy Calculations for Highly Glazed Designs
When architectural designs exceed the standard 25% glazing allowance, an accredited energy assessor runs a Standard Assessment Procedure (SAP) calculation.
The assessor demonstrates that upgraded insulation elsewhere (such as installing triple glazing, upgrading loft insulation to 400mm, or adding high-efficiency solar panels) offsets the heat loss through extensive glass areas.